Initial Startup

Initial Startup and
Programming Procedures
Ensure that the cover is installed before operating
the PENTEK INTELLIDRIVE.
Most installations will only require the initial
startup settings. However, the installer may need
to set additional parameters. Information about
accessing all parameters, explanations of their
functions, and procedures for changing parameter
values, will be found later in this section.
1. Program the Drive: Apply power to the
PENTEK INTELLIDRIVE. Setup Guide will appear
in the display. Follow keypress sequence shown in
Figure 10.
NOTICE If Setup Guide does not appear, refer to
Drive Reset Procedure, Figure 20.
Apply 230V to Drive
Enter Motor Phase
(1 Phase or 3 Phase)
Press Enter
1 Phase
Connection Type
(2 Wire or 3 Wire)
Press Enter
Enter Service
Factor Amps
Press Enter
Set Time
Press Enter
Set Date
Press Enter
Setup Complete
Figure 10 - Drive Setup Guide.
3 Phase
Motor Type
Subm or Above Gnd
Service Factor Amps
To maximize pump performance, be sure to
enter the correct Service Factor Amps (SF Amps)
in the PENTEK INTELLIDRIVE.
• Entering SF Amps higher than the motor rating
lets the Drive supply more amps to the motor
than the motor is designed for and may allow
the motor to overheat (see Table 4).
• Entering SF Amps lower than the motor rating
limits the output amps to less than the motor is
designed for and will reduce the performance
of the pump.
• For any 1-Phase 3-Wire motor, the correct
Service Factor Amp rating for the Drive is Cap
Start/Cap Run amps (see Table 4). This may
not match the motor nameplate, which (for a
Single Phase, 3-Wire motor) will generally be
Cap Start/ Induction Run Amps.
• For any 3-Phase or 1 Phase, 2-Wire motor, use
the motor nameplate Service Factor Amp rating.
NOTICE PENTEK
differ from motors of the same horsepower
from other manufacturers. For 1-Phase, 3-Wire
motors from all other submersible motor
manufacturers, enter the motor manufacturer's
CS/CR service factor amps for your motor.
For 3-Phase or 2-Wire 1-Phase motors, use the
motor nameplate amp value. Also see Retro Fit
Applications. (Table 7)
2. Select 80 Hz Operation, if necessary (See 60 Hz
to 80 Hz Operation for more information):
A. Press MAIN MENU button.
B. Follow the keypress sequence shown in
Figure 11.
6566 0512
Figure 11 - Select 80 Hz
(3-phase submersible operation only).
submersible motors may
®
Press MAIN MENU
button
Use arrows to
scroll to Motor
Press Enter
Use arrows to select
Max Frequency
Press Enter
Use arrows to
select 80 Hz
Press Enter
to save
6570 0512_EN
10