Electrical data
Power (low overload LO)
Line voltage
Line frequency
Overload capability of frame sizes A – C
(low overload LO)
Overload capability of frame sizes D – F
(low overload LO)
Rated input current
(LO: at 40 ℃)
Base-load current
LO: at 40 ℃)
Operating temperature
Relative humidity
Output frequency
Pulse frequency
Frequency range that can be skipped
Fixed frequencies
Digital inputs and outputs
Short-circuit current rating (SCCR)
Technical data
Functional data
0.75 to 90 kW
380 to 480 V 3 AC ±10 %
47 to 63 Hz
1.5 x base-load current (150 %) for 3 s every
300 s
1.1 x base-load current (110%) for 57 s every
300 s
1.1 x base-load current (110%) for 60 s every
300 s
2.3 to 166 A (IP55)
2.3 to 135 A (IP20)
2.2 to 178 A (IP55)
2.2 to 145 A (IP20)
0 to 60 °C while derating
(see derating factors)
< 95% RH, non-condensing
0 to 550 Hz
4 kHz (default) to 16 kHz. The pulse frequency
can be changed manually in 2 kHz steps.
4, parameterizable
15, parameterizable
6 DI
3 DO (2 x 230 V AC / 2 A, 1 x 30 V DC /
0.5 A)
4 AI (2 x 0 to 10 V / -10 to 10 V / 0 to 20 mA /
4 to 20 mA, 1 x 0 to 20 mA / 4 to 20 mA /
Pt1000 / LG-Ni1000, 1 x Pt1000 /
LG-Ni1000)
2 AO (0 to 10 V / 0 to 20 mA / 4 to 20 mA)
1 x KTY/PTC/ThermoClick sensor
2 x PSU-out (10 VDC, 24 VDC)
1 x PSU-in (24 VDC)
IP55 FSA - FSC: 40kA
IP55 FSD - FSF: 65kA
IP20 FSA - FSF: 65kA
9
93 | 98
A5E36496664A_d