8.3.2 Fault table (SW)

Siemens
Building Technologies
The flashing frequencies of the LEDs have the following meaning:
LED
RDY
BF
Green – steady light
Off
Green – Slow
Off
Red – Fast
Off
Red – Fast
Red – Fast
Green – steady light
Red – steady light
Green – steady light
Red – Slow
Green – steady light
Red – Fast
The table below contains only an excerpt from the list of alarms and faults. The
complete list of alarms and faults can be found in List Manual CU230P
(A5E02297932A AE).
Types of fault
Device faults fall into two different categories:
Alarms:Alarms have no direct effect on the variable speed drive and disappear
once the cause has been removed The device and motor continue operating
normally. Alarms do not need to be acknowledged.
Faults: A fault indicates a severe fault during variable speed drive operation. In
the event of a fault, the connected motor is shut down instantaneously.
Operation cannot resume until the fault has been cleared and the fault
message acknowledged.
Alarms
Number
Cause
A01028
Configuration error
A01098
The power supply for the
Control Unit was interrupted
for a longer period.
A01590
Motor maintenance interval
lapsed
A01900
PROFIBUS: Configuration
telegram faulty
Service, maintenance and fault rectification
Fault rectification
Description
No fault
Commissioning or reset to factory settings
No fault
Incorrect memory card
Receive process data
Bus active – no process data
No bus activity
Solution
Parameterization on the memory card has been created
with a different type of module (order number, MLFB).
Check the module parameters and recommission if
necessary.
1.
Set the date and time of day of the real-time clock:
p8400 (RTC time), p8401 (RTC date)
2.
Deactivate the alarm: p8405 = 0.
Carry out maintenance and reset the maintenance
interval (p0651).
A PROFIBUS master is attempting to establish a
connection with a faulty configuration telegram.
Check the bus configuration on the master and slave
side.
8
81 | 98
A5E36496664A_d
2016-03-17