Conformity - Siemens G120P Technical Manual

Variable speed drive
Table of Contents

Advertisement

Technical data
9

Conformity

9.2 Conformity
94 | 98
Siemens
Building Technologies
Mechanical data
Vibratory load
Transport (in transport packaging) according
to EN 60721-3-2
Operation
Test values according to EN 60068-2-6
Shock stressing
Transport (in transport packaging) according
to EN 60721-3-2
All devices and components
Operation
Test values according to EN 60068-2-6
Frame sizes A to F
Environmental conditions
Protection class according to EN 61800-5-1
Touch protection according to EN 61800-5-1
Permissible ambient and coolant temperature (air)
during operation for line-side power components
and Power Modules
Low overload
(low overload LO)
High overload
(high overload HO)
Permissible ambient and coolant temperature (air)
during operation for Control Units and
supplementary system components
Class 2M3
Class 3M2
Class 2M3
Class 3M2
Class I (with protective conductor system) and
Class III (PELV)
If used as intended
See derating factors for derating
0 to 40 °C (32 to 104 °F) without derating
> 40 to 60 °C (104 to 160 °F) with derating
0 to 50 °C (32 to 122 °F) without derating
> 50 to 60 °C (122 to 160 °F) with derating
With CU230P-2: 0 to 60 °C (32 to 140 °F)
With IOP-2: 0 to 50 °C (32 to 122 °F)
With BOP-2: 0 to 50 °C (32 to 122 °F)
With blanking cover: 0 to 60 °C (32 to 140 °F)
Up to 2000 m above sea level
A5E36496664A_d
2016-03-17