Battery Replacement Smf6120 - Siemens FDCW221 Technical Manual

Radio gateway
Hide thumbs Also See for FDCW221:
Table of Contents

Advertisement

Maintenance / Troubleshooting
9.3

Battery replacement SMF6120

44
Building Technologies
Fire Safety & Security Systems
The two battteries of the manual call point with radio base must be replaced when
a battery fault for the manual call point with radio base is indicated on the control
panel.
The batteries must only be replaced by qualified personnel.
Always replace both batteries.
Prerequisites:
The FDnet detector line or the detector zone must be switched off.
The radio gateway must be in normal operation.
The new 3.6V batteries for the SMF6120 are ready for insertion.
Batteries of the manual call points with radio base must be exchanged one after the other.
Only one manual call point of a radio cell may be without batteries at the same time, and only for a
short period.
Procedure:
1. Open the manual call point with radio base SMF6120
2. Remove the old batteries from the SMF6120.
3. Wait for the discharge period of 10 seconds.
4. Insert the new batteries in the SMF6120 and close the SMF6120 again.
The status indicator shows the field strength by flashing during 2 minutes.
For additional information, please consult the catalogue sheet SMF6120, document
no. 007564,
order no. A24205-A337-A886.
see also:
5.8 Status indication on the radio detector DOW1171/SMF6120, Page 24
Fig. 14 , Page 40
009865_b_en_--.doc
11.2007

Advertisement

Table of Contents
loading

Table of Contents