Commissioning
8.8

Resetting the SMF6120 in delivery condition

40
Building Technologies
Fire Safety & Security Systems
The manual call point with radio base SMF6120 is made up of the following parts:
- Manual call point SMF121 (upper part)
- Radio base SMF6120 (lower part)
The manual call point with radio base is reset in the delivery condition. All existing configurations are
deleted.
1
2
Fig. 13
Interior view of the manual call point SMF121
Legend
1
Resetting slider
2
Alarm button
1
2
3
Interior view of the radio base SMF6120
Fig. 14
Legend
1
Registration button 'New'
2
Connectors of the batteries
3
Status indicator
4
3.6V lithium Mignon batteries
4
009865_b_en_--.doc