Table 7 Recommended Airflow; Table 8 Indoor Blower Performance; Table 9 Maximum Esp Electric Heat Only; Table 10 Electric Heat - Bard K36A2-A Installation Instructions Manual

Wall-mounted packaged
Table of Contents

Advertisement

Manual 2100-628
Page
24 of 24
RECOMMENDED AIRFLOW
Nominal
Model
Rated
CFM *
K36A, K36L
1100
K42A, K42L
1300
K48A, K48L
1550
K60A, K60L
1600
* Rated CFM and ESP on factory speed connection.
INDOOR BLOWER PERFORMANCE
Model
K36
ESP
(Inch H
0)
2
0.1
1100
0.2
1068
0.3
1030
0.4
983
0.5
924
NOTE: Application of required supply and return grilles
will result in approximately 0.10" ESP restriction.
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
Model
Outlet
Speed
-A0Z
-A05
-N0Z
-N06
Values shown are for units equipped with standard
1-inch throwaway filter or 1-inch washable filter.
Derate ESP by .15 for 2-inch pleated filters.
ELECTRIC HEAT
240V-1
KW
Amps
BTUH
5
20.8
17,065
6
--
--
TABLE 7
Nominal
Recommended
Rated
Airflow Range
ESP *
.15
930 - 1350
.20
1485 - 1070
.20
1750 - 1285
.20
1890 - 1335
TABLE 8
K42
K48
K60
1300
1550
1650
1257
1485
1587
1208
1413
1518
1149
1313
1440
1079
1240
1350
TABLE 9
K36A/L, K42A/L,
K48A/L, K60A/L
FRONT
High
Low
.50
.50
.50
.50
.50
.50
.50
.50
TABLE 10
208V-1
Amps
BTUH
Amps
18.1
12,800
--
--
400V-3
BTUH
--
--
9.0
21,330