19 Install condensate line

Prepare condensate trap assembly
densate.
1. Remov
2. See Figures 54, 55 and 56. The figures below shows the installa-
3. Install the inspection coupling
tighten securely.
4.
B
drain tube (item
), See Figure 55. Push the flexible tube (item
approximately 1-3/4" (Figure 55
Figure 54.
Figure 54
Figure 55
The condensate trap must be in place during all op-
condensate outlet and that the condensate discharge
line is in good condition and installed per this man-
ual. Failure to comply could result in severe per-
sonal injury, death or substantial property damage.
Part number 550-142-850/0716
M
-
OUNT GAS
FIRED WATER BOILER
A
and gasket as shown. Finger
Boiler Manual
Figure 56
-
B
)
5. Fill the air-trap with approximately 1/2 quart (0.5
to the condensate drain system
Condensate drain system
1.
flexible drain line will fit in a ¾" PVC coupling. Run
pump.
Use materials approved by the authority having
D1785, F441 or D2665. Cement and primer
2.
should have an overflow switch to prevent property
FreeStyle®
Style® 155.
3. When sizing condensate pumps, make sure to include
The condensate line must remain unob-
ing in potential water damage to property.
Install a neutralizing filter when draining into
. The
FreeStyle® 80,
Free-
-
47