33 Maintenance

Disconnect power
Electrical shock hazard — Discon-
nect all electrical power to the boiler
cedures. Failure to complete could
result in severe personal injury, death
or substantial proper t y damage.
Jacket side panels are now
removeable for servicing
are removeable, and can be removed by re-
moving the screws onthe top and bottom
Re-install boiler jacket door
after startup or servicing
up or servicing. The boiler jacket door
side the boiler room. This is particularly
same room as other appliances.
Failure to keep the jacket door securely
personal injury or death.
Start-up and check/out
Removing and reinstalling components
maintenance procedure, you must prove
the boiler is operating correctly. To do
boiler and system start-up, beginning on
page 67
Failure to comply could result in severe
personal injury, death or substantial
property damage.
Part number 550-142-850/0716
M
-
OUNT GAS
FIRED WATER BOILER
-
-
Boiler Manual
Clean condensate trap
1. See Figure 131.
2. Disconnect top cleanout cap nut that secures the trap body to
the boiler condensate connection.
3. Remove the cleanout cap.
4.
5. Re-assemble gasket and clean out cap.
6.
7. Reattach the trap to the boiler condensate drain outlet. Check
Figure 131
Condensate
drain line
Inspect and clean ignition electrode
Wait until heat exchanger/boiler is cooled down
injury.
1. Disconnect the ground wire and ignition cable connected to
Remove the ignitor wire by pulling on the connector, not the wire.
Figure 132
103