Installation Drawing (0K7803-D 2 of 2)

AIR OUTLET
HOLE LOCATIONS FOR
OPTIONAL MOUNTING TO
A CONCRETE PAD
16.0 [5/8] DIA. CLEARANCE
HOLE (4) PLACES,
3/8 DIA. MASONRY ANCHOR
BOLTS RECOMMENDED
RIGHT SIDE VIEW
40
AIR INTAKE
TOP VIEW
250.0
[9.8]
446.6
[17.6]
FRONT OF UNIT
FUEL INLET - 3/4" NPT
REQUIRED FUEL PRESSURE: NATURAL GAS : 3.5-7" WATER COLUMN
179.0
300.4
[7.0]
[11.8]
457.2
[18.0]
MINIMUM OPEN AREA
ON SIDES AND FRONT
575.3
[22.7]
530.0
[20.9]
44.8
378.7
[1.8]
[14.9]
LIQUID PROPANE (VAPOR) : 10-12" WATER COLUMN
MAIN AC/CONTROL WIRING HOLE FOR 3/4" CONDUIT
MAIN AC/CONTROL WIRING HOLE FOR 1 1/4" CONDUIT
REAR VIEW
Installation Guidelines For 60 Hz Air-cooled Generators
914 [36.0]
AIR INTAKE
**ALL DIMENSIONS IN:
MILLIMETERS [INCHES]