10. FIELD SETTING

<Field setting must be made from the remote controller in accordance with the installation condi-
tion.>
• Setting can be made by changing the "Mode No.", "FIRST CODE NO." and "SECOND CODE NO.".
• For setting procedures and instructions, refer to the "FIELD SETTING" in the installation manual of the
remote controller.
1. Setting external static pressure
• Change the SECOND CODE No. according to Table 3 depending on the resistance of the connecting duct.
(SECOND CODE NO. is factory set to "01" normal.)
Table 3
External static pressure
Normal: 49Pa (5 mmH
High static pressure:
88/108Pa (9/11 mmH
Low static pressure: 20Pa
(2 mmH
O)
2
2. Setting with installing optional accessories
• Refer to the installation manual of the optional accessories for the optional accessories installation.
3. Setting air filter sign
• Remote controllers are equipped with liquid crystal display air filer signs to display the time to clean air
filters.
• Change the SECOND CODE No. according to Table 4 depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to "01" for filter contamination-light)
Table 4
Setting
Air filter
contamination-light
Air filter
contamination-heavy
4. When implementing group control
• When using as a pair unit or as a parent unit for simultaneous operation multi, you may simultaneous
start/stop (group) control up to 16 unit with the remote controller.
• In this case, all the indoor units in the group will operate in accordance with the group control remote
controller.
• Select a remote controller which matches as many of the functions (swing flap, etc) in the group as
possible.
Wiring Method
(1)Remove the control box lids. (See ''8. ELECTRIC WIRING WORK''.)
(2)Cross-wire the terminal block for remote controller (P
polarity.) (Refer to Fig. 22 on page 15 and Table 2 on page 12)
English
Mode No.
O)
2
O)
13 (23)
2
Spacing time of display air filter
sign (long life type)
Approx. 2500 hrs
Approx. 1250 hrs
Indoor unit 1
Indoor unit 2
Group control remote control
FIRST CODE NO.
6
FIRST CODE
Mode No.
10 (20)
Indoor unit 3
Fig. 24
P
) inside the control box. (There is no
1
2
FIRST CODE NO.
01
02
03
SECOND
NO.
CODE NO.
01
0
02
16