Flue Pipe Installation - Buderus Logano G124X II/SP Installation And Maintenance Instructions Manual

Hide thumbs Also See for Logano G124X II/SP:
Table of Contents

Advertisement

10

Flue pipe installation

10 Flue pipe installation
This section describes the connection of the flue pipe.
Note that the draft hood cannot be modified.
1. Mount flue pipe on the flue connection of the draft
hood and fasten with four (4) corrosion-resistant
sheet metal screws.
The vent damper supplied with the boiler must be used
for venting the boiler only.
USER NOTE
In Canada the vent damper must not be
installed on a propane-fired heating
system with an electronic ignition system.
The position of the vent damper must be visible.
The back flow check must be at least six inches from all
flammable components.
The vent damper must be freely accessible for
maintenance.
The vent damper must be open when the main burner of
the boiler is operating.
Installation of vent damper
2. Install pins in the hole of the vent baffle.
3. Fasten vent damper to the flue pipe of the back flow
check with three (3) corrosion-resistant sheet metal
screws.
Connecting flue pipe
4. Connect flue pipe to the chimney with the shortest
possible length of flue pipe.
Use only flue pipes with a suitable diameter for the
boiler.
Every horizontal section of the flue pipe must have a
minimum rise of 1/4 inch per foot towards the chimney.
The flue pipe must be securely fastened to prevent it
from hanging. A support must be installed at least every
five feet. Fasten every connection with at least three (3)
corrosion-resistance sheet metal screws. The end
section of the flue pipe must connect to the inside of the
chimney smoke duct.
A minimum clearance of 18" is required between the flue
pipes and all flammable materials.
The flue pipe must not be reduced in size and venting
must not be prevented by the installation of additional
components.
26
Installation and maintenance instructions Logano G124X II/SP special gas-fired boiler • Issue 04/2005
3
2
1
Fig. 23 Installation of vent baffle
1 Open draft hood
2 Vent damper
3 Position indicator
4 Motor
5 Draft hood
6 Boiler
We reserve the right to make any changes due to technical modifications.
4
5
6