Error Log Clear - Omron SYSMAC CJ1W-EIP21 Operation Manual

Sysmac cs and cj series ethernet/ip units 100base-tx 100base-tx/10base-t
Hide thumbs Also See for SYSMAC CJ1W-EIP21:
Table of Contents

Advertisement

FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports
1st byte
Error code
Detailed
information
Error Code, Detailed Information
Details of the error stored in the record. Refer to 14-4-4 Error Log Error Codes for details.
Minute, Second, Day, Hour, Year, Month
Indicate the time at which the error stored in the record occurred.
Precautions
• If the error log contains fewer records than the number specified in the number of records parameter, all
records stored in the error log at the time the command is executed will be returned and the command exe-
cuted will end normally.
Response Codes
Response code
0000
Normal end
1001
Command too large
1002
Command too small
1103
Beginning record number is out of range
110C
The number of read records is 0.

ERROR LOG CLEAR

Clears the error log for the EtherNet/IP Unit or built-in EtherNet/IP ports, and resets the number of stored
records to 0.
Command Block
21 03
Command code
Response Block
21 03
Command
Response
code
code
Response Codes
Response code
0000
Normal end
1001
Command too large
PING
Performs processing equivalent to a UNIX computer's PING command (see below).
10th byte
Day Hour Year Month
Minutes Second
Description
Description
Appendix E
399

Advertisement

Table of Contents
loading

Table of Contents