Indoor Fan Motor Control; In Cooling Operation - Toshiba RAS-B10EKVP-E Service Manual

Split type
Hide thumbs Also See for RAS-B10EKVP-E:

Advertisement

Ilmalämpöpumppujen myynti, huolto ja asennus: Jäähdytinpalvelu RefGroup Oy.
Item
2. Indoor fan
<In cooling operation>
motor control
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
COOL ON
Fan speed setup
Ta
[ ˚C ]
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
Lue lisää nettisivuiltamme: www.ilmalämpöpumput.com
Operation flow and applicable data, etc.
MANUAL
Indication
AUTO
L
L+
M
M+
H
Air volume AUTO
M+(WB)
*3
a
b
*4
c
*5
d
L(W6)
e
(Table 1) Indoor fan air flow rate
(Fig. 1)
Fan speed
W6
(L + M) / 2
W9
(M + H) / 2
WC
(Fig. 2)
*3 : Fan speed =
(M + –L) x 3/4 + L
*4 : Fan speed =
(M + –L) x 2/4 + L
*5 : Fan speed =
(M + –L) x 1/4 + L
(Linear approximation
from M+ and L)
– 28 –
Description
* Symbols
UH
: Ultra High
H
: High
M+
: Medium+
M
: Medium
L+
: Low+
L
: Low
L-
: Low–
UL
: Ultra Low
SUL
: Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and
heat exchanger temperature.