Minimum Clearance To Combustible Materials - Regency F3500 Owners & Installation Manual

Pro series freestanding woodstove
Table of Contents

Advertisement

installation

MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS

Please read the section below carefully as clearances depend on whether the Airmate or the Rear Heat Deflector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall.
Clearances may only be reduced by means approved by the regulatory authority.
Note: Minimum ceiling height roof - 83" (2108 mm)
NOTE: This clearance is also required for air space between the appliance and wall/ceiling.
ROOF EXIT
F
WALL EXIT
Residential Installation "C" Vent (Single Wall Pipe)
F3500
with Airmate or
Rear Deflector
Residential Close Clearance (To be installed with required pipe components) Listed Double Wall Pipe
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove collar to the ceiling level.
F3500
with Airmate or
Rear Deflector
Mobile Home Close Clearance (To be installed with required pipe components) Listed Double Wall Pipe
the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove collar to the ceiling level.
Refer to Mobile Home Installation in this manual.
F3500
with Airmate or
Rear Deflector
Minimum Alcove Clearance to Combustible Materials
The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height - 83" (2108 mm) Vertical Termination}
H = Maximum depth of alcove - 48" (1219mm)
G= Minimum width of alcove - 60" (1524mm)
NOTE: This clearance is also required for air space between the appliance and wall/ceiling.
8
C
A
D
A
B
11"
9-1/2"
279mm
241mm
A
B
11"
9-1/2"
279mm
241mm
A
B
11"
9-1/2"
279mm
241mm
NOTE:
NOTE:
ROOF EXIT
WALL EXIT
C
D
8"
24"
203mm
610mm
C
D
8"
24"
203mm
610mm
C
D
8"
24"
203mm
610mm
Be aware that local Codes and
Regulations may override some
clearances listed in this manual.
Check with your local inspector.
Clearances to combustibles are for
the safety of the property. To avoid
overheating and damaging the
appliance these clearances should
be maintained for non-combustibles
also.
E
16"
20-1/2"
406mm
521mm
E
16"
20-1/2"
406mm
521mm
E
16"
20-1/2"
406mm
521mm
A
ROOF EXIT
WALL EXIT
D
G
F3500 Regency Freestanding Woodstove
F
F
When
F