9-2. DRY OPERATION

TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
ERROR CODE
û Fû C
°F °C
ONLY1Hr.
TEMP.
MENU
ON/OFF
BACK
MONITOR/SET
DAY
PAR-21MAA
CLOCK
OPERATION
Control modes
1-1. Thermo regulating function (Function to prevent restarting for 3 minutes)
1. Thermo regulating
function
1-2. Freeze prevention control
Indoor fan operation controll depends on the compressor conditions.
2. Fan
Note: Remote controller setting is not acceptable.
3. Drain pump
Same control as COOL operation
Same control as COOL operation
4. Vane
(up/down vane change)
<How to operate>
1 Press POWER ON/OFF button.
Hr
ON
AFTER
OFF
2 Press the operation MODE button to display DRY.
FUNCTION
FILTER
3 Press the TEMP. button to set the desired temperature.
WEEKLY
SIMPLE
AUTO OFF
NOTE: The set temperature changes 1°F(2°F) when the
ON/OFF
FILTER
CHECK
TEST
CLEAR
Setting the Dry thermo by the thermo regulating signal and the room
temperature (TH21).
Dry thermo ON Room temperature
Dry thermo OFF Room temperature
3 min. passed since starting operation
Room
temperature
Thermo regulating signal Room temperature (T1)
ON
Over 64°F
OFF
Less than 64°F
No control function
Dry thermo
Fan speed notch
ON
OFF
pressed once. Dry 67 to 87°F
Variable range of the set temprature depends on the remote controller
which is applied.
Control details
desired temperature + 2°F
desired temperature
T1
83°F
83°F > T1
79°F
79°F > T1
75°F
75°F > T1
Unconditional
Dry thermo OFF
[Low]
Stop
17
or
Dry thermo
Dry thermo
ON
OFF
time (min)
time (min)
9
3
7
3
5
3
3
3
3
10
button is
Remarks