4-3. ELECTRICAL PARTS SPECIFICATIONS
Model
Parts name
Thermistor
(Room temperature
detection)
Thermistor
(Pipe temperature
detection/ Liquid)
Thermistor
(Pipe temperature
detection/ Gas)
Fuse
(Indoor controller board)
Fan motor
(with Thermal fuse)
Fan motor capacitor
Vane motor
Drain pump
Drain sensor
Linear expansion valve
[coil]
Electric heater
(Condensation proof)
Power supply terminal
block
Transmission terminal
block
MA remote controller
terminal block
Note: Refer to WIRING DIAGRAM for the supplied voltage.
PLFY-P08NCMU-E.TH
Symbol
PLFY-P08NCMU-E
PLFY-P08NCMU-ER2.TH
TH21
Resistance 30 F/15.8k , 50 F/9.6k , 70 F/6.0k , 80 F/4.8k , 90 F/3.9k , 100 F/3.2k
TH22
Resistance 30 F/15.8k , 50 F/9.6k , 70 F/6.0k , 80 F/4.8k , 90 F/3.9k , 100 F/3.2k
TH23
Resistance 30 F/15.8k , 50 F/9.6k , 70 F/6.0k , 80 F/4.8k , 90 F/3.9k , 100 F/3.2k
FUSE
6-pole OUTPUT 15W
PK6N15-LA
MF
C1
MV
DP
DS
Thermistor resistance 30 F/6.3k , 50 F/3.9k , 70 F/2.5k , 80 F/2.0k , 90 F/1.6k , 100 F/1.3k
DC12V Stepping motor drive, Port dimension 3.2 (0~2000pulse)
LEV
H2
TB2
TB5
TB15
PLFY-P12NCMU-E.TH
.TH
PLFY-P12NCMU-E
1
PLFY-P12NCMU-ER2.TH
250V 6.3A
6-pole OUTPUT 20W
PK6N20-LA
Thermal fuse
OFF 284 F
1.5
× 440V
MSBPC20M13
DC12V 300 /phase
PLD-12230ME-1
INPUT 12/10.8W 24 /Hr
EDM-40YGME
240V 15W
(L1, L2,GR) Rated to 330V 30A
(M1, M2, S) Rated to 250V 20A
(1, 2) Rated to 250V 10A
8
PLFY-P15NCMU-E.TH
.TH
PLFY-P15NCMU-E
1
PLFY-P15NCMU-ER2.TH
6-pole OUTPUT 20W
PK6N21-LA
36 F
.TH
1