Mitsubishi Electric City Multi PLFY-P08NCMU-E Technical & Service Manual page 23

City multi series ceiling cassettes
Hide thumbs Also See for City Multi PLFY-P08NCMU-E:
Table of Contents

Advertisement

<Thermistor characteristic graph>
Thermistor for
lower temperature
Thermistor R
=15k' ± 3%
0
Fixed number of B=3480 ± 2%
Rt=15exp { 3480(
273+(t-32)/1.8
30_F
15.8k'
50_F
9.6k'
70_F
6.0k'
80_F
4.8k'
90_F
3.9k'
100_F
3.2k'
Thermistor for
drain sensor
Thermistor R
=6.0k' ±5%
0
Fixed number of B=3390 ± 2%
Rt=6exp { 3390(
273+(t-32)/1.8
30_F
6.3k'
50_F
3.9k'
70_F
2.5k'
80_F
2.0k'
90_F
1.6k'
100_F
1.3k'
Linear expansion valve
1 Operation summary of the linear expansion valve
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
Linear expansion valve
M
5
1
White
Red
Orange
Room temperature thermistor(TH21)
Liquid pipe temperature thermistor(TH22)
Gas pipe temperature thermistor(TH23)
1
1
) }
273
1
1
) }
273
Blue
4
4
Brown
6
3
Yellow
2
2
3
1
50
40
30
20
10
10
Brown
Red
Blue
Orange
Yellow
White
Connector (CN60)
23
< Thermistor for lower temperature >
0
-20
0
20
40
60
80
100
Temperature (°F)
< Thermistor for drain sensor >
9
8
7
6
5
4
3
2
1
0
20
40
60
80
100
120
140 170
Temperature (°F)
Controller board
DC12V
6
5
Drive circuit
4
4
3
3
2
2
1
1
120

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

City multi plfy-p12ncmu-eCity multi plfy-p15ncmu-

Table of Contents