Control modes
2-3. Thermo OFF mode
2. Fan
When the thermoregulating function changes to OFF, the indoor fan operates in
[Extra low].
2-4. Heat defrosting mode
The indoor fan stops.
3. Drain pump
No drain pump operation
However, when the control changes from COOL or DRY operation, the drain pump
operates for 3 minutes.
(1) Initial setting : OFF → HEAT···[last setting]
4. Vane control
(Up/down vane
change)
(2) Vane position :
Horizontal →Downward A →Downward B →Downward C→Swing
(3) Restriction of vane position
The vane is horizontally fixed for the following modes.
(The setting by the remote controller is temporarily invalidated and vane control is
set by the unit controller.)
• Thermo OFF
• Hot adjust [Extra low] mode
• Heat defrost mode
Control details
When changing the mode from exception of HEAT to HEAT operation
···[Downward C]