10-3. TEST POINT DIAGRAM
10-3-1. Indoor power board
PLFY-P08NCMU-E.TH
PLFY-P08NCMU-E
.TH
1
PLFY-P08NCMU-ER2.TH PLFY-P12NCMU-ER2.TH
Operation by switch
SW11
How to set addresses
0
Example: If address is "3", remain SW12
(for over 10) at "0", and match SW11 (for 1 to 9)
with "3".
1
How to set branch numbers SW14 (Series R2 only)
Match the indoor unit's refrigerant pipe with
the BC controller's end connection number.
Remain other than series R2 at "0".
PLFY-P12NCMU-E.TH
PLFY-P12NCMU-E
1

PLFY-P15NCMU-E.TH

.TH
PLFY-P15NCMU-E
PLFY-P15NCMU-ER2.TH
CN2S
Connect to the indoor controller board (CN2D)
Between 1 to 3 12.5-13.7V DC (Pin1 (+))
CNSK
Connect to the indoor controller board (CNDK)
Between 1 to 3 208-230V AC
26
Effective
Remarks
timing
Indoor controller board
<Initial setting>
SW12
0
Before
power
supply
Indoor controller board
ON
<Initial setting>
SW14
.TH
1
SW11
0
0