Viessmann VITOLADENS 300-W Installation And Service Instructions Manual page 97

Wall mounted oil condensing boiler
Table of Contents

Advertisement

Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
58
No DHW heating by
the boiler
90
Control mode
91
Control mode
92
No solar DHW heat-
ing
93
Control mode
94
No solar DHW heat-
ing
98
Control mode
99
Control mode
9A
No solar DHW heat-
ing
9b
Control mode
9C
No solar DHW heat-
ing
9E
Control mode
Cause
Lead break, cylin-
der temperature
sensor
Short circuit, tem-
perature sensor /
Short circuit, tem-
perature sensor
Short circuit, col-
lector temperature
sensor
Short circuit, cylin-
der temperature
sensor
Short circuit, cylin-
der temperature
sensor
Lead break, tem-
perature sensor /
Lead break, tem-
perature sensor
Lead break, collec-
tor temperature
sensor
Lead break, cylin-
der temperature
sensor
Lead break, cylin-
der temperature
sensor
No flow rate in col-
lector circuit or flow
rate too low, or
temperature limiter
has responded
Troubleshooting
Measures
Check sensors (see
page 105)
Check sensor / on solar
control module
Check sensor aÖ on solar
control module
Check temperature sen-
sor & on solar control
module or sensor on the
Vitosolic
Check temperature sen-
sor at connection S3 to
the Vitosolic.
Check temperature sen-
sor % on solar control
module or sensor on the
Vitosolic
Check sensor / on solar
control module
Check sensor aÖ on solar
control module
Check temperature sen-
sor & on solar control
module or sensor on the
Vitosolic
Check temperature sen-
sor at connection S3 to
the Vitosolic.
Check temperature sen-
sor % on solar control
module or sensor on the
Vitosolic
Check solar circuit pump
and solar circuit. Acknowl-
edge fault message