Further details regarding the individual steps
Standard values for burner adjustment
Note
Check that the service instructions are
valid for the relevant burner (see applic-
ability on the last page and the serial no.
on the boiler type plate).
A Flue gas test port
Rated heating out-
put
Burner stage
Rated heating out-
put
Oil burner nozzle
Make: Danfoss
Oil pressure approx.
*1
Max. permissible
vacuum
in the oil line
Oil throughput
approx.
Static burner pres-
sure approx.
CO
content approx.
2
■ Test value w/o cov-
er panel
*1
Due to nozzle tolerances and varying oil characteristics, the oil pressure may vary
from the specified values.
Commissioning, inspection, maintenance
A
kW
12.9/19.3
Stage 1
kW
12.9
Type
80°H LE V
Gph
bar
8.0-10.5
MPa
0.8-1.05
bar
0.35
kPa
35
kg/h
1.05
l/h
1.24
mbar
8.0-10.5
kPa
0.8-1.05
%
12.2-13.4
(cont.)
Stage 2
Stage 1
19.3
0.40
14.0-17.5
9.0-13.5
1.4-1.75
0.9-1.35
0.35
35
1.58
1.86
15.5-19.5
11.0-15.5
1.55-1.95
1.1-1.55
16.1/23.5
Stage 2
16.1
23.5
80°H LE V
0.50
16.0-18.5
1.6-1.85
0.35
0.35
35
35
1.53
1.92
1.80
2.26
17.5-21.0
1.75-2.1
12.2-13.2
31