Boiler - Viessmann VITOLADENS 300-W Installation And Service Instructions Manual

Wall mounted oil condensing boiler
Table of Contents

Advertisement

Code 2
General
(cont.)
Coding in the delivered condition
9C:20
Monitoring LON subscrib-
ers
If there is no response
from a subscriber after
20 min, the values speci-
fied inside the control unit
are used. Only then will a
fault message be issued
9F:8
Differential temperature
8 K; only in conjunction
with a mixer circuit

Boiler

Coding
Coding in the delivered condition
04:1
Minimum burner pause
time subject to the boiler
load (specified by boiler
coding card)
06:...
Maximum limit of the boil-
er water temperature, de-
faulted in °C by the boiler
coding card
0d:0
Do not adjust
0E:0
Do not adjust
21:0
No service interval (hours
run) selected
23:0
No interval for burner
service
74
Possible change
9C:0
No monitoring
9C:5
Time adjustable from 5 to
to
60 min
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
Possible change
04:0
Minimum burner pause
time set permanently
(specified by boiler coding
card)
06:20
Maximum limit of the boiler
to
water temperature within
06:127
the ranges specified by the
boiler
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10 000 h.
One adjusting step ≙
100 h
23:1
Interval adjustable from 1
to
to 24 months.
23:24