14 D .H .W . Flow Switch, Filter And Flow Limiter; Function; Description And Location Of Parts - (Figure 14.2); Removal Of The Sensor - Biasi Inovia ERP Series Service Manual

G.c. appl. no. 47-583-38, 47-583-39, 47-583-40, 41-583-30
Table of Contents

Advertisement

D.h.w. flow switch, filter anD flow limiter
14 d .h .w . flOw switch, filter and flOw
limiter

14 .1 function

The d.h.w. flow switch A in Figure 14.1 is a device that generates
an electrical signal when hot water is drawn.
figure 14 .1
When the flow rate through the d.h.w. circuit reaches about 2,5
litres/min', the sensor closes the electric contact that switches
the boiler d.h.w operation ON.
14 .2 description and location of parts - (figure
14 .2)
1 Flow switch plug
2 O-ring
3 Flow limiter (Inovia 30C ERP. Inovia 35C ERP. optional ac-
cessory)
4 Body with flow meter turbine
5 Filter
1
2
3
figure 14 .2

14 .3 removal of the sensor

warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent .
figure 14 .3
a
1 Remove the front panel of the case.
2 Disconnect the connectors B and remove the sensor holder
3 Remove the sensor.

14 .4 checks

5
figure 14 .4
4
2
1 Remove the front panel of the case.
2 Don't disconnect the connectors B
3 Measure the electrical frequency at the leads of the sensor.
C (Figure 14.3).
warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent .
Sensor operation
0..32 Hz
(without flow rate)
33..200 Hz
(witht flow rate)
wh = white
bu = blue
rd = red
Without flow rate the electrical frequency must be 0÷32Hz.
With flow rate the electrical frequency must be 33÷200Hz.
e
d
b
c
bu
wh
rd
b
5V
rd
wh
- 37 -