(4) Duct connected-High static pressure type (FDU)

(a) Single type
Model
Item
Power source
Operation data
Nominal capacity
kW
Power consumption
kW
Running current
Power factor
%
Inrush current
Sound Pressure Level
dB(A)
Exterior dimensions
mm
Height × Width × Depth
Exterior appearance
(Munsell color)
Net weight
kg
Refrigerant equipment
Compressor type & Q'ty
Starting method
Refrigerant oil
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor <Starting method>
W
Air flow (Standard)
CMM
External static pressure
Pa
Outdoor air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Electric heater
W
Remote controller
Room temperature control
Safety equipment
Installation data
mm
Refrigerant piping size
Connecting method
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant Quantity
Drain pump
Drain
Insulation for piping
IP code
Standard Accessories
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
Cooling
27˚C
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to
ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz
(5) External static pressure can be changed from standard external static pressure (factory setting) to maximum external static
pressuer (high static pressure setting) by remote controller.
(6) Value of sound pressure level become increased 5dB(A), when external static pressure is 130Pa.
Indoor unit FDU71VD
Cooling
7.1 [ 3.2 (Min.)~8.0 (Max.)]
2.15
A
9.6
A
Hi : 41 Lo : 37
295 × 850 × 650
Louver fin & inner grooved tubing
Centrifugal fan × 2
230 < Direct line start >
Hi : 20 Lo : 17
Standard : 60 Max : 130
Possible (on return duct)
Procure locally
Rubber sleeve (for fan motor)
Polyurethane form
Thermostat by electronics
Internal thermostat for fan motor
Frost protection thermostat
Liquid line : I/U φ9.52 (3/8")
Gas line
Flare piping
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
R410A 2.95kg in outdoor unit (incl. the amount for the piping of : 30m)
Built-in Drain pump
Hose Connectable with VP20
IPXO
Drain hose
Outdoor air temperature
DB
WB
DB
19˚C
35˚C
20˚C
7˚C
FDU71VNXVD
98
5 < Max.running current 17 >
40
wired : RC-E5 (option) wireless : RCN-KIT3-E (option)
Pipe φ9.52 (3/8") × 0.8
: I/U φ15.88 (5/8") Pipe φ15.88 (5/8") × 1.0 O/U φ15.88 (5/8")
Max.50m
Necessary (both Liquid & Gas lines)
External static pressure
of indoor unit [Pa]
WB
24˚C
6˚C
54
-
-
'12 • PAC-T-173
Adapted to RoHS directive
Outdoor unit FDC71VNX
220-240V~50Hz
Heating
8.0 [ 3.6 (Min.)~9.0 (Max.)]
2.15
9.5
99
Cooling : 51, Heating : 48
750 × 880 (+88) × 340
Stucco White
(4.2Y7.5/1.1) near equivalent
60
RMT5118MDE2 × 1
Direct line start
0.675 (M-MA68)
M shape fin & inner grooved tubing
Electronic expansion valve
Propeller fan × 1
86 < Direct line start >
Cooling : 60, Heating : 50
0
Rubber sleeve (for Compressor)
20 (Crank case heater)
Internal thermostat for fan motor
Abnormal discharge temperature protection.
O/U φ9.52 (3/8")
Flare piping
See page 152
Holes size φ20 × 3pcs
IP24
60
PJD001Z311