(4) High static pressure duct type (FDU)

(a) Single type
Model FDUVA802HES1R
Item
Nominal cooling capacity
(1)
Nominal heating capacity
(1)
Power source
Cooling power consumption
Running current (Cooling)
Power factor (Cooling)
Heating power consumption
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
Model
kW
kW
kW
A
%
kW
A
%
A
dB(A)
mm
kg
kW
kg
r
W
CMM
W
Wired remote control switch (Optional : RC-E1R)
mm
(in)
Connectable with VP25 (I.D.25mm, O.D.32mm)
Item
Indoor air temperature
DB
27˚C
20˚C
FDUVA802HES1R
FDUA801R
20.0 [7.0~22.4]
22.4 [7.6~25.0]
3 Phase, 380/400/415V 50Hz
48
360 × 1570 × 830
92
Louver fin & inner grooved tubing
Microcomputer controlled de-icer
Multiblade centrifugal × 4
200 × 2
Direct line start
51
Available
Field purchased
Rubber sleeve (for fan motor)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
Liquid line: φ9.52 (3/8") Gas line: φ25.4 (1")
Brazing piping (Outdoor liquid piping: Flare)
Necessary (both Liquid & Gas lines)
Mounting kit. Drain hose
Decorative Panel
Outdoor air temperature
WB
DB
19˚C
35˚C
7˚C
31
-
-
FDCVA802HESR
6.50
10.5
89
6.32
10.6
86
5
57
1300 × 970 × 370
122
GT-C5150ND79
4.5
Direct line start
Straight fin & inner grooved tubing
Electronic expansion valve
R410A
5.4 [Pre-charged up to the piping length of 30m]
1.45 (M-MA32R)
Propeller fan × 2
120 × 2
Direct line start
Cooling: 150, Heating: 145
Rubber mount (for compressor)
40 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Abnormal discharge temperature protection.
WB
24˚C
6˚C
Standards
ISO-T1

Hide quick links: