(2) Ceiling cassette-4way compact type (FDTC)

(a) Single type
FDTC40ZJXVF
Model
Indoor unit
Cool Mode
Outdoor
18 °C DB
21 °C DB
air temp.
12 °C WB
14 °C WB
°C DB
TC
SHC
TC
SHC
11
13
15
17
19
21
23
25
3.73 3.20 3.89 3.09 4.08 3.31 4.20 3.29 4.34 3.27 4.61 3.45 4.89 3.40
27
3.76 3.21 3.93 3.11 4.13 3.33 4.25 3.31 4.36 3.28 4.60 3.44
29
3.70 3.19 3.86 3.08 4.06 3.30 4.18 3.28 4.30 3.25 4.54 3.42
31
3.64 3.16 3.80 3.05 4.00 3.28 4.12 3.26 4.24 3.23 4.48 3.40
33
3.23 2.85 3.44 3.06 3.74 3.03 3.94 3.25 4.06 3.23 4.18 3.21 4.42 3.38
35
3.28 2.88 3.44 3.06 3.68 3.00 3.88 3.23 4.00 3.21 4.12 3.19 4.36 3.36
37
3.23 2.85 3.38 3.04 3.62 2.98 3.82 3.20 3.94 3.19 4.06 3.17 4.30 3.34
39
3.17 2.82 3.32 3.01 3.56 2.95 3.76 3.18 3.88 3.16 4.00 3.14 4.23 3.32
41
3.12 2.80 3.27 2.99 3.50 2.93 3.70 3.16 3.82 3.14 3.93 3.12 4.17 3.30
43
3.06 2.77 3.21 2.96 3.44 2.90 3.64 3.13 3.76 3.12 3.87 3.10 4.10 3.27
FDTC50ZJXVF
Model
Indoor unit
Cool Mode
Outdoor
18 °C DB
21 °C DB
air temp.
12 °C WB
14 °C WB
°C DB
TC
SHC
TC
SHC
11
13
15
17
19
21
23
25
4.66 3.72 4.86 3.60 5.10 3.81 5.25 3.79 5.42 3.77 5.76 3.95 6.11 3.89
27
4.70 3.74 4.91 3.62 5.16 3.84 5.31 3.81 5.46 3.79 5.75 3.95
29
4.62 3.70 4.83 3.59 5.08 3.81 5.23 3.78 5.38 3.75 5.68 3.92
31
4.54 3.66 4.75 3.55 5.00 3.77 5.15 3.75 5.30 3.72 5.60 3.89
33
4.04 3.32 4.31 3.55 4.67 3.51 4.93 3.74 5.08 3.72 5.23 3.69 5.53 3.87
35
4.11 3.36 4.30 3.54 4.59 3.48 4.85 3.71 5.00 3.69 5.15 3.66 5.45 3.84
37
4.04 3.32 4.23 3.51 4.52 3.44 4.77 3.67 4.92 3.65 5.07 3.63 5.37 3.81
39
3.97 3.29 4.16 3.48 4.45 3.41 4.70 3.64 4.85 3.63 4.99 3.60 5.29 3.78
41
3.90 3.25 4.09 3.44 4.38 3.38 4.62 3.61 4.77 3.59 4.92 3.57 5.21 3.75
43
3.83 3.22 4.01 3.40 4.30 3.34 4.55 3.58 4.69 3.56 4.84 3.54 5.13 3.72
Note(1) These data show average statuses.
Note(1)
Depending on the system control, there may be ranges where the operation is not conducted continuously.
Note(1)
These data show the case where the operation frequency of a compressor is fixed.
(2) Capacities are based on the following conditions.
(2)
Corresponding refrigerant piping length :7.5m
(2)
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity
SHC : Sensible heat capacity
FDTC40VF
Outdoor unit
Indoor air temperature
23 °C DB
26 °C DB
27 °C DB
16 °C WB
18 °C WB
19 °C WB
TC
SHC
TC
SHC
TC
3.38 2.87 3.56 3.10 3.65 3.08 3.75 3.05 3.95 3.22 4.15 3.17
3.46 2.91 3.65 3.14 3.75 3.11 3.85 3.09 4.05 3.26 4.26 3.20
3.54 2.94 3.74 3.17 3.84 3.15 3.95 3.13 4.15 3.29 4.36 3.23
3.62 2.98 3.83 3.21 3.94 3.19 4.04 3.16 4.26 3.33 4.47 3.27
3.69 3.01 3.91 3.24 4.02 3.22 4.15 3.20 4.41 3.38 4.67 3.33
3.81 3.06 3.99 3.27 4.10 3.25 4.26 3.24 4.56 3.43 4.87 3.39
3.85 3.08 4.04 3.29 4.15 3.27 4.30 3.25 4.59 3.44 4.88 3.40
FDTC50VF
Outdoor unit
Indoor air temperature
23 °C DB
26 °C DB
27 °C DB
16 °C WB
18 °C WB
19 °C WB
TC
SHC
TC
SHC
TC
SHC
4.22 3.31 4.45 3.54 4.56 3.51 4.69 3.48 4.94 3.66 5.19 3.59
4.32 3.35 4.56 3.59 4.68 3.56 4.81 3.53 5.07 3.70 5.32 3.63
4.42 3.40 4.68 3.64 4.80 3.61 4.93 3.58 5.19 3.75 5.45 3.67
4.53 3.45 4.79 3.68 4.92 3.65 5.06 3.63 5.32 3.79 5.58 3.72
4.62 3.49 4.89 3.73 5.02 3.70 5.19 3.68 5.51 3.86 5.84 3.80
4.76 3.55 4.99 3.77 5.13 3.74 5.32 3.73 5.70 3.93 6.09 3.89
4.81 3.58 5.04 3.79 5.19 3.77 5.37 3.75 5.73 3.94 6.10 3.89
SRC40ZJX-S
28 °C DB
31 °C DB
20 °C WB
22 °C WB
SHC
TC
SHC
TC
SHC
SRC50ZJX-S
28 °C DB
31 °C DB
20 °C WB
22 °C WB
TC
SHC
TC
SHC
TC
164
-
-
(kW)
Heat Mode
Indoor air temperature
Outdoor
air temp.
33 °C DB
°C DB °C WB 16
24 °C WB
TC
SHC
-19.8 -20
-17.7 -18
-15.7 -16
-13.5 -14
2.67 2.63 2.59 2.55 2.50
-11.5 -12
2.83 2.79 2.75 2.71 2.67
-9.5
-10
3.00 2.96 2.92 2.88 2.84
-7.5
-8
3.17 3.13 3.09 3.05 3.01
-5.5
-6
3.23 3.20 3.16 3.12 3.09
-3.0
-4
3.29 3.26 3.23 3.20 3.17
-1.0
-2
3.36 3.33 3.30 3.28 3.25
1.0
0
3.42 3.40 3.38 3.35 3.33
2.0
1
3.45 3.43 3.41 3.39 3.37
3.0
2
3.67 3.65 3.63 3.61 3.59
5.0
4
4.11 4.09 4.07 4.04 4.01
7.0
6
4.55 4.53 4.50 4.47 4.44
9.0
8
4.78 4.75 4.72 4.69 4.66
11.5
10
5.01 4.98 4.95 4.91 4.88
13.5
12
5.30 5.26 5.21 5.14 5.10
15.5
14
5.58 5.53 5.48 5.37 5.32
16.5
16
5.73 5.67 5.61 5.48 5.44
Heat Mode
(kW)
Outdoor
Indoor air temperature
33 °C DB
air temp.
24 °C WB
°C DB °C WB 16
SHC
-19.8 -20
-17.7 -18
-15.7 -16
-13.5 -14
3.20 3.15 3.11 3.05 3.00
-11.5 -12
3.40 3.35 3.31 3.26 3.20
-9.5
-10
3.60 3.55 3.51 3.46 3.41
-7.5
-8
3.80 3.75 3.71 3.66 3.61
-5.5
-6
3.88 3.83 3.79 3.75 3.71
-3.0
-4
3.95 3.92 3.88 3.84 3.80
-1.0
-2
4.03 4.00 3.97 3.93 3.90
1.0
0
4.10 4.08 4.05 4.03 4.00
2.0
1
4.14 4.12 4.10 4.07 4.05
3.0
2
4.41 4.38 4.36 4.33 4.30
5.0
4
4.94 4.91 4.88 4.85 4.82
7.0
6
5.46 5.43 5.40 5.37 5.33
9.0
8
5.74 5.70 5.67 5.63 5.59
11.5
10
6.02 5.98 5.94 5.89 5.85
13.5
12
6.36 6.31 6.25 6.17 6.12
15.5
14
6.70 6.64 6.57 6.44 6.39
16.5
16
6.87 6.80 6.73 6.58 6.52
'12 • PAC-T-173
(kW)
°C DB
18
20
22
24
PJA003Z382
A
(kW)
°C DB
18
20
22
24
PJA003Z382
A