Ceiling Suspended Type (Fden) - Mitsubishi Heavy Industries FDT40VF Technical Manual

Hide thumbs Also See for FDT40VF:
Table of Contents

Advertisement

(3) Ceiling suspended type (FDEN)

(a) Single type
Model
Item
Power source
Operation data
Nominal capacity
kW
Power consumption
kW
Running current
Power factor
%
Inrush current
Sound Pressure Level
dB(A)
Exterior dimensions
mm
Height × Width × Depth
Exterior appearance
(Munsell color)
Net weight
kg
Refrigerant equipment
Compressor type & Q'ty
Starting method
Refrigerant oil
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor <Starting method>
W
Air flow (Standard)
CMM
External static pressure
Pa
Outdoor air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Electric heater
W
Remote controller
Room temperature control
Safety equipment
Installation data
mm
Refrigerant piping size
Connecting method
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant Quantity
Drain pump
Drain
Insulation for piping
IP code
Standard Accessories
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
Cooling
27˚C
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
Indoor unit FDEN40VF
Cooling
4.0 [ 1.1 (Min.)~4.7 (Max.)]
1.02
A
4.8 / 5.0
92 / 93
A
P-Hi : 46 Hi : 39 Me : 38 Lo : 37
210 × 1,070 × 690
Plaster White
(6.8Y8.9/0.2) near equivalent
Louver fin & inner grooved tubing
Centrifugal fan × 2
25 < Direct line start >
P-Hi : 11 Hi : 10 Me : 9 Lo : 7
Not possible
Pocket plastic net × 2 (Washable)
Rubber sleeve (for fan motor)
Polyurethane form
wired : RC-EX1A (option) wired : RC-E5 (option) wireless : RCN-E1R (option)
Thermostat by electronics
Internal thermostat for fan motor
Frost protection thermostat
Liquid line : I/Uφ6.35 (1/4") Pipeφ6.35 (1/4") × 0.8 O/Uφ6.35 (1/4")
Gas line
Flare piping
Max.20m (Outdoor unit is higher)
Max.20m (Outdoor unit is lower)
R410A 1.5kg in outdoor unit (incl. the amount for the piping of : 15m)
Hose Connectable with VP20
IPXO
Mounting kit, Drain hose
Outdoor air temperature
DB
WB
DB
19˚C
35˚C
20˚C
7˚C
FDEN40ZJXVF
5 < Max.running current 12 >
28
0
φ12.7 (1/2")
φ12.7 (1/2") × 0.8
:
Max.30m
Necessary (both Liquid & Gas lines)
WB
24˚C
6˚C
35
-
-
'12 • PAC-T-173
Adapted to RoHS directive
Outdoor unit SRC40ZJX-S
220-240V~50Hz / 220V~60Hz
Heating
4.5 [ 0.6 (Min.)~5.4 (Max.)]
1.10
5.2 / 5.5
92 / 91
50
640 × 800 (+71) × 290
Stucco White
(4.2Y7.5/1.1) near equivalent
45
RMT5113MCE2 (Twin Rotary type) × 1
Direct line start
0.45 MA68
M shape fin & inner grooved tubing
Capillary tubes + Electronic expansion valve
Propeller fan × 1
34 < Direct line start >
Cooling : 36 Heating : 33
0
Rubber sleeve (for Compressor)
Internal thermostat for fan motor
Abnormal discharge temperature protection.
φ12.7 (1/2")
Flare piping
See page 152
Holes size φ20 × 5pcs
IPX4
Drain elbow, Drain hole grommet
PFA003Z954
A