5-8. Electrical Service Guide

Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
Input Voltage (V)
Input Amperes (A) At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 2011 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 "Time-Delay" fuses are UL class "RK5" . See UL 248.
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amps), and UL class "H" ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.

5-9. Extension Cord Data (Use Shortest Cord Possible)

.
When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
Input Power
Phase
Input Voltage
115 V
1
115 V
1
115 V
1
230 V
1
.
A complete Parts List is available at www.HobartWelders.com
1
2
Time-Delay Fuses
3
Normal Operating Fuses
4
4
Hertz
60
60
60
60
Conductor Size
14 AWG
12 AWG
10 AWG
14 AWG
Elec Serv 2011−08
60 Hz Single Phase
230 Volts AC
115 Volts AC
24
A 20 ampere
individual branch
30
circuit
protected by
35
time-delay fuses
14
or circuit breaker
is required.
53
See Section 4-3
(16)
14
Max. Cord Length
25 ft (8 m)
55 ft (17 m)
100 ft (30 m)
53 ft (16 m)
OM-260 274 Page 17