Location; General; Low-Fire Only Installation - Carrier 58MVP080 Installation, Start-Up, And Operating Instructions Manual

111 series
Table of Contents

Advertisement

PRESSURE SWITCH TUBING
One collector box pressure tube (pink label) is factory connected to
the pressure switch for use when furnace is installed in UPFLOW
or HORIZONTAL LEFT applications. This tube MUST be dis-
connected and used for the condensate trap relief port tube. The
other collector box pressure tube (green label) which was factory
connected to the condensate trap relief port connection MUST be
connected to the pressure switch in DOWNFLOW or HORIZON-
TAL RIGHT applications.
NOTE: See Fig. 11 or tube routing label on main furnace door to
check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to
pressure switch.
2. Use small diameter tube (factory supplied in loose parts bag)
to extend collector box pressure tube (green label) which was
previously connected to condensate trap relief port connec-
tion.
3. Connect collector box pressure tube (green label) to pressure
switch connection labeled COLLECTOR BOX.
4. Use remaining small diameter tube (factory supplied in loose
parts bag) to extend collector box pressure tube (pink label)
which was previously connected to pressure switch.
5. Route this extended tube (pink label) to condensate trap relief
port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
CONSTRUCT A WORKING PLATFORM
Construct working platform where all required furnace clearances
are met. (See Fig. 3 and 10.)
The condensate trap MUST be installed below furnace. See
Fig. 4 for dimensions. The drain connection to condensate
trap must also be properly sloped to an open drain.
NOTE: Combustion-air and vent pipes are restricted to a mini-
mum length of 5 ft. (See Table 5.)
NOTE: A 12-in. minimum horizontal pipe section is recom-
mended with short (5 to 8 ft) vent systems. This recommendation
is to reduce excessive condensate droplets from exiting the vent
pipe. (See Fig. 10 or 29.)

LOCATION

Step 1—General
When a furnace is installed so that supply ducts carry air to areas
outside the space containing the furnace, return air must also be
handled by ducts sealed to furnace casing. The ducts terminate
outside the space containing the furnace to ensure there will not be
a negative pressure condition within equipment room or space.
Furnace may be located in a confined space without special
provisions for dilution or ventilation air. This furnace must be
installed so electrical components are protected from water.
Locate furnace as close to center of air distribution system as
possible.
Locate furnace so combustion-air pipe lengths are not exceeded.
Refer to Table 5.
FRONT
NOTE: These furnaces are designed for a minimum continuous
return-air temperature of 60°F or intermittent operation down to 55°F
such as when used with a night setback thermostat. Return-air
temperature must not exceed a maximum of 85°F. Failure to follow
these return-air temperature limits may affect reliability of heat
exchangers, motors, and controls.
NOTE: For proper furnace operation, install furnace so that it is
level or pitched forward within 1/2 in. to ensure proper condensate
drainage from secondary heat exchangers.
If these furnaces are used during construction when adhe-
sives, sealers, and/or new carpets are being installed, make
sure all combustion and circulating air requirements are
followed. If operation of furnace is required during construc-
tion, use clean outside air for combustion and ventilation.
Compounds of chlorine and fluorine, when burned with
combustion air, form acids which will cause corrosion of heat
exchangers. Some of these compounds are found in paneling,
dry wall adhesives, paints, thinners, masonry cleaning mate-
rials, and many other solvents commonly used in construction
process.
Provide ample space for servicing and cleaning. Always comply
with minimum fire protection clearances shown on units clearance
to combustibles label. (See Fig. 3.) Locate furnace where available
electric power and gas supplies meet specifications on furnace
rating plate.
Step 2—Low-Fire Only Installation
This 58MVP furnace can be installed to operate in the low-fire
only heating mode when sized using the low-fire heating capacity.
This is accomplished by placing setup switch SW-2 in the ON
11
°F
°F
RETURN
AIR
MAX 85°F
MIN 55°F
A93042
A93025

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

58mvp10058mvp04058mvp060

Table of Contents