Installation; Step 1 - Select Location - Carrier 58ED Installation, Start-Up And Service Instructions Manual

Horizontal gas-fired furnaces
Table of Contents

Advertisement

HEATING A COOLING
58ED,PB
Horizontal Gas-Fired Furnaces
American Gas Association, 1515 Wilson Boulevard,
Arlington, VA 22209.
A
WARNING
The furnace cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. The unit
must also be electrically grounded in accordance
with local codes, with the National Electrical Codes
ANSI/NFPA No. 70-1984 or the latest edition. Do
not use gas piping as an electrical ground.
INSTALLATION
Step 1 — Select Location
— This furnace may be
located in an attic, basement crawl space, alcove or
suspended from the ceiling of a utility room or basement.
As shown in Table 3, the minimum clearances, or greater,
must be provided between the furnace and adjacent
construction.
A WARNING
Failure to comply with all the recommended clear¬
ances will result in a fire hazard.
If a furnace is to be installed in a residential garage, it
must be installed so the burners and the ignition source
are located not less than 18 in. above the floor and the
furnace must be located or protected to avoid physical
damage by vehicles.
The furnace should be located as close to the chimney
as possible in order to keep vent connections as short and
direct as possible. The furnace should also be located as
near to the center of the air distribution as possible, and
should be mounted level.
Since this furnace is suitable for attic installation, it
must not be installed directly on carpeting, tile or other
combustible material. Line contact is only permissible
between lines formed by the intersection of the furnace
top and two sides and the building joists, studs or
framing. See Fig. 2
A clearance of at least 30 in. should be provided at the
front of the furnace for combustion air and servicing.
For attic installations, the passageway and service area
adjacent to the furnace should have a floor installed.
The areas adjacent to the combustion air openings must
be covered with fireproof board or sheet metal extending
a minimum of 12 in. from the furnace. See Fig. 2.
If the furnace is to be installed in a crawl space, consult
local codes. Use of a concrete pad one to 2 in. thick is
recommended.
If the furnace is to be suspended from the ceiling, it is
necessary to use steel pipe straps around each end of the
furnace. These straps should be attached to the furnace
with sheet metal screws and bolted to the rafters. The
furnace may also be suspended by an angle iron frame
bolted to the rafters.
->
Table 2 — Blower Data (Direct Drive)
FURNACE 58ED/PB
050
075
100
125
140
SERIES (15th Digit
A
C
A
B
C
A
B
C
C
D
B
C
of Model No.)
BLOWER SIZE (in )
_ _
DXW
10x4
10x4
10x6
10x6
10x6
10x6
10x8
10x8
10x8
12 x 9
12x9
12 x 12
12x12
MOTOR HP (PSC)
%
'A
%
%
A
%
%
A
'4
Vt
%
1
^
%
SPEED TAP
Lo
Hi
Lo
Hi
Lo
Lo
Hi
Med
Hi
Med
Lo
Hi
Med
Hi
Med
Hi
Med
Hi
Med
Hi
Med
Hi
Med
WIRE COLOR
Red
Blk
Red
Blk
Red
Red
Blk
Blu
Blk
Blu
Red
Blk
Biu
Blk
Blu
Blk
Blu
Blk
Blu
Blk
Blu
Blk
Blu
BLOWER RPM
830
1070
760
1080
700
920
1020
790
1060
820
860
990
730
1050
840
1070
820
1000
920
1070
970
980
780
EXTERNAL STATIC
PRESSURE (in wg)
20
50
20
50
20
20
50
20
50
20
20
50
20
50
20
50
20
50
20
50
20
50
20
AIRFLOW (Cfm)
765 | 930 |
I
7 35
M
I/MJ 11165 |l 130 | |
995
11260 | 1090 | 1310 11290
1090 | 1530 [ 1360 | | 2010 | 1860
1 2115
| 1810 12100 | 1930 | 2350 | 2100
A
WARNING
When operating furnace in heating mode, thestatic pressure
and the temperature rise (outlet air temperature minus room
temperature) must be within those limits specified on the
AGA rating plate.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book II
14
PC 101
Catalog No 535-834
Printed in U S A
Form 58ED.PB-1SI
Pg 2
6-85
Replaces: 58PB-1 SI
Tab
l6a 18a
For replacement items use Carrier Specified Parts