Types of cables and minimum thicknesses
Connection
Control panel power supply 230V
Motor power supply 24 V DC
Flashing light
Photocell transmitters
Photocell receivers
Accessory power supply
Control and security devices
Antenna connection
N.B.: If the cables differ in length compared to what is shown in the table, the cable cross-section is determined according
to the actual current draw of the devices connected and according to the provisions of the IEC EN 60204-1 standard.
For connections that require several, sequential loads, the sizes given on the table must be re-evaluated based on actual
power draw and distances. When connecting products that are not specified in this manual, please refer to the documen-
tation provided with said products.
Type of
Cable length
cable
1 < 10 m
3G x 1.5 mm²
4G x 1,5 mm²
FROR CEI
2 x 0.5 mm²
20-22
2 x 0.5 mm²
IEC EN
4 x 0.5 mm²
50267-2-1
2 x 0.5 mm²
2 x 0.5 mm²
RG58
The data and information provided in this manual are subject to change at any time without prior notice.
Cable length
Cable length
10 < 20 m
20 < 30 m
3G x 2.5 mm²
3G x 4 mm²
4G x 1.5 mm²
4G x 2.5 mm²
2 x 1 mm²
2 x 1.5 mm²
2 x 0.5 mm²
2 x 0.5 mm²
4 x 0.5 mm²
4 x 0.5 mm²
2 x 0.5 mm²
2 x 1 mm²
2 x 0.5 mm²
2 x 0.5 mm²
max. 10 m