Remote Control Extension; Remote Control Extension Id; Termination Switch - Bosch Plena Operating Manual

Table of Contents

Advertisement

86
en | Configuration
6.6

Remote control extension

The remote control extensions are configured using an ID selector and a switch:
3
Figure 6.9: Remote control settings
6.6.1

Remote control extension ID

The ID of the remote control extension is set using a ID selector. The remote control extension
only controls the voice alarm router that has the same ID. Furthermore, each remote control
extension that is connected to the same remote control must have a unique ID.
6.6.2

Termination switch

The last remote control extension in a sequence of looped-through remote control extensions
must always be terminated. Only for these remote control extensions, put the termination
switch in the ON position.
Notice!
The Controller comes with a termination plug (RJ45). Plug this connector in the unused RJ45
socket.
2013.07 | V2.0 |
RCP ext. In
Termination
ID
On
Off
6
1...9
Installation and Operation manual
RCP ext. Out
Plena
Bosch Security Systems B.V.