VENTING INTRODUCTION

The HZ42STE uses the "balanced flue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer
liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm
room air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate
solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.

VENTING ARRANGEMENTS

ALLOWABLE HORIZONTAL TERMINATIONS FOR HZ42 ST

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 45º and one 90º (two 45
90
) for direct horizontal runs with horizontal termination use only one 45º elbow.
o
Note: Must use optional rigid pipe adapter (Part# 510-994) when using Rigid Pipe Venting Systems.
0
18
16
14
12
10
8
6
4
2
0
VENT RESTRICTOR SETTING:
Vent restrictor factory set, no adjustment required unless otherwise indicated.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 1 or Set 2 if required.
Note: Regency
Direct Vent System (Flex) is only approved for horizontal terminations.
®
Maintain clearances to combustibles as listed in "Clearances" section
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever passing through a wall.
A wall thimble is mandatory for all horizontal terminations due to high temperatures.
Flex system can only be used up to 10 feet - otherwise rigid venting must be used.
Horizontal (Feet)
2
4
6
8
SET 2
SET 0
SET 1
(factory setting)
3 " (
6 914
mm)
Minimum Height
Requirement
14
16
10
12
Regency Horizon™ HZ42STE-10 Gas Fireplace
installation
elbows equal to one
o
18
20
center
of hole
C L
C L
Please note the minimum centerline for
basic install shown above.
|
25
|
25