Power supply
(cont.)
Control unit power supply
A Terminals in the control panel
Compressor power supply
A Terminals at the control module
Instantaneous heating water heater power supply
A Terminals in the control panel
Installation sequence
Note
This supply must never be blocked
Max. fuse rating 16 A
Recommended core cross-section:
2
1.5 mm
Note
The upstream fuses must have Z
characteristics.
Max. fuse rating 16 A
Recommended core cross-section:
2
6 kW : 1.5 mm
2
9 kW : 2.5 mm
The three heating elements are
switched by inserting jumpers across
X60.8, X60.9 and X60.10 in star for-
mation and must be connected to N.
77