Condensate

Condensate can form in high efficiency direct vent
appliances. Without proper drainage, condensate will
damage the heat exchanger.
To prevent condensate damage, follow these
instructions.
DO NOT
Do not connect the condensate drain pipe directly
to the rain sewer.
Do not connect the condensate drain line with an
air conditioning evaporator coil drain.
MUST DO
Use only venting that is approved and identified as
acceptable for your particular model.
Slope the venting toward the appliance according
to the vent manufacturer's installation
instructions.
All condensate must drain and be disposed of
according to local codes.
Use only corrosion resistant materials for the
condensate drain lines such as PVC pipe or plastic
hose.
The condensate drain pipe (along its entire length)
must be at least the same diameter as the drain
line, (1/2 inch NPT).
The end of the condensate drain pipe should be
open to the atmosphere. The end should not be
under water or other substances.
To minimize freezing of the condensate in outdoor
units, run the condensate drain line through an
interior wall or between insulation and an interior
wall.
It is recommended that the condensate trap drain
line be insulated. A frozen condensate trap results
in a diagnostic code 25.
INFORMATION
Water heaters have an integrated condensate
collector.
Regions of cold climate will create more
condensate in the vent system.
The condensate drain pipe should be as short as
possible and have a downward pitch.
If the condensate drain gets blocked, a diagnostic
code will display on the controller or status
monitor. If this occurs, the condensate drain must
be cleaned.
The condensate trap will automatically prime (self-
prime) during operation of the unit as condensate
forms. Condensate draining from the unit
indicates that the trap is full and that there is no
blockage in the condensate drain. It is not
necessary to add water to the condensate trap.
A condensate neutralizer kit, 804000074, is
available from Rinnai. The kit allows condensate
to flow through neutralizing media that raises the
pH of the condensate to a level that will help
prevent corrosion of the drain and public sewer
system.
Checklist for Venting and
Condensate (indoor models only)
Verify proper clearances around the vents and air
intakes.
For indoor models, ensure SW4 in DIPSW2 is set
to the appropriate venting style.
Ensure you have used the correct venting
products for the model installed and that you
have completely followed the venting
manufacturer's installation instructions and these
installation instructions.
Verify that the vent system does not exceed the
maximum length for the number of elbows used.