Flue Installation with Centrotherm Venting (indoor models only)
Install the venting termination according to the diagrams and instructions below.
Comply with the exhaust clearances found in this Rinnai Installation and Operation Manual.
Only one appliance can be attached to the vent system.
Install the system according to the Centrotherm installation instructions included with the vent system.
The vent termination and air intake must be in the same pressure zone.
Do not exceed the maximum straight vent length with number of elbows as shown in the tables in the
following section.
Maintain the clearances shown in the figures below.
The following vent materials are NOT APPROVED for use with this appliance:
WARNING
Failure to use approved vent materials can result in property damage, personal injury, or death.
Slope horizontal exhaust run towards the water heater 1/4" per foot. DO NOT slope combustion air pipe towards unit. Be
sure to dispose of condensate per local codes.
Cellular core PVC/CPVC
Radel, ABS, and/or Galvanized ducts.
Vertical Termination
Horizontal Termination
KCM Series Manual
5"
Vent
11
"
Intake
Optional
19