Setting Error Of Option Switch In Indoor Unit - Samsung DVM Series Service Manual

System air conditioner
Hide thumbs Also See for DVM Series:
Table of Contents

Advertisement

8-2-24. Setting error of option switch in indoor unit

Outdoor unit display
Indoor unit display
Judgment method
Causes
The error is occurred when the option switch for using the remote controller, No.1 switch on SW03, is set and the wired remote controller address
is different from the RMC address of indoor unit.
Check setting of the SW03.
Is the address of the wired
remote controller and the RMC address of the
indoor unit is the same?
Reset the address of the
wired remote controller
to "1".
Reset the power of indoor unit.
(Operation)
(Timer)
(Fan)
- Switch setting error for using the wired remote controller
- Option switch setting error of indoor unit
No
Check the switches of the wired
remote controller and the
indoor unit, then replace the
remote controller and/or the
indoor unit PCB.
- 191 -
(Filter)
(Removing frost)
Yes
Reset the address of the RMC
address of the indoor unit to "1".
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents