Refrigerating Cycle Diagram

6-1-3. Main parts status

1. Digital scroll compressor
The variable capacity type compressor to control the capacity up to 10 ~ 100% with 19 steps.
2. Accumulator
To prevent the incoming of the liquid refrigerant to the compressor (prevention of liquid back).
3. Receiver
To reduce the noise by flowing the high pressure liquid refrigerant to the high pressure pipe and to control the amount of
refrigerant during the individual operation of indoor unit.
4. Solenoid valve (PWM)
It is installed at the top of digital scroll compressor and at the low pressure pipe, which is used for operating the digital scroll
compressor. When the valve is open, the digital scroll compressor keeps the state of unloading.
5. Solenoid valve (HGBV)
When the low pressure gets lower, the valve is open by the low pressure safety device. The valve is open in order to reduce
the load at the start of compressor and when the system stops and then keep the balance of low pressure.
6. Solenoid valve (LBV)
When the compressor is overheated, it actuates to lower the temperature of compressor for stable operation.
7. Solenoid valve (VBV)
The valve is open in order to reduce the load at the start of compressor and when the system stops and then keeps the
balance of low pressure.
8. High pressure switch
To stop the system for the system protection when the high pressure exceeds the set value.
9. Low pressure switch
To stop the system for the system protection when the low pressure falls below the set value.
10. Temperature sensor (DTS, Discharge Temperature Sensor)
10.
It is the means to measure the refrigerant temperature of compressor outlet which is used as the data for control of
compressor.
11. Temperature sensor (CMS, Condenser Mid Sensor)
10.
It is the detection means to do the optimum control of outdoor fan, which is used as the data for each
protection or initial startup.
12. Temperature sensor (COS, Condenser Out Sensor)
10.
It is used as the detection for calculation of over-cooling at the condenser outlet which is referred for the
adjustment of refrigerant during refrigerant charging.
13. Temperature sensor (OATS, Outdoor Air Temperature Sensor)
10.
To measure the outdoor temperature which is used for the determination of start method.
14. Fixed scroll compressor
10.
The fixed capacity type compressor.
15. Temperature sensor (FDTS, Fixed Discharge Temperature Sensor)
10.
It is the means to measure the refrigerant temperature of compressor outlet which is used as the data for control of fixed
compressor.
16. Low pressure sensor (LPSO)
10.
By measuring the low pressure, any abnormal system status is determined and the low-pressure
protection control is performed.
17. High pressure sensor (HPSO)
10.
By measuring the high pressure, any abnormal system status is determined and the high-pressure
protection control is performed.
18. Oil separator
10.
This device recovers oils emitted from the compressor and returns it to the compressor again.
19. Oil sensor (OIL.S)
10.
To control EEV against liquid back and low dilution of oil to protect the compressor by measuring
the temperature of oil used for controlling SUMP at low temperature in cooling / heating mode.