Indoor Unit Freezing Protection - Samsung DVM Series Service Manual

System air conditioner
Hide thumbs Also See for DVM Series:
Table of Contents

Advertisement

8-2-61. Indoor unit freezing protection

Outdoor unit display
Indoor unit display
Judgment method
Causes
If the outdoor temperature is so low(below -5˚C) or a number of indoor unit is off simultaneously, the indoor unit can be frozen in an instant.
Check the indoor unit detected
freezing.
Remove the obstacles of
corresponding indoor unit and clean
the dust filter.
Error reset(KEY3)
Operate a corresponding
indoor unit.
Does operate normally the
indoor unit fan motor?
Yes
Test operation for every
room(KEY 4)
Is high/low pressure normal ?
Yes
It is completed to check the system.
(Operation)
(Timer)
- When the temperature of indoor unit heat exchanger on cooling operation maintains
-
over 5 minutes below -4˚C
- Indoor fan motor defect or lock
- EEV open error
No
motor output terminal normal?
Replace the motor after checking
the connection wire of fan motor.
- 229 -
(Fan)
(Filter)
(Removing frost)
Is the voltage of PCB fan
Yes
No
After checking the quantity of
refrigerant, if needed recharge
the refrigerant.
Troubleshooting
No
Restart after PCB
exchange.