Outdoor Unit's Option Switch Setting Error. (E-560) - Samsung AM053FXMDCH Service Manual

System air conditioner
Hide thumbs Also See for AM053FXMDCH:
Table of Contents

Advertisement

3-35. Outdoor unit's option switch setting error.
(Using E2P option of other models or emergency operation for compressor malfunction
option setting was enabled on all compressors of corresponding outdoor unit) (E-560)
Outdoor unit Display
Judgement Method
Cause of problem
Is the Compressor
breakdown setting value is
Is the outdoor unit
EEPROM accurately connected to
connector?
Download relevant model EEPROM and then reset.
Execute automatic commissioning for UP
cancellation after EEPROM download
74
(E2P option use of other model or set of the relevant outdoor unit, compressor
breakdown)
"not set"?
Yes
Yes
E-560
Set the compressor breakdown setting value as"not set".
No
When setting breakdown for repair and replace
of compressor : Change the setting after replace.
No
Connect outdoor unit EEPROM and then reset.
Samsung Electronics