11-3 Malfunciton code
• For places where the malfunction code is left blank, the "
continues operating, be sure to inspect the system and make repairs as necessary.
• Depending on the type of indoor or outdoor unit, the malfunction code may or may not be displayed.
Code
A1
Indoor unit's PC board faulty
A3
Drain water level abnormal
A5
Freeze-up protector "or stopped by high pressure control"
A6
Indoor fan motor overloaded, overcurrent or locked
AF
Humidifier faulty
Air cleaner faulty
AH
Only the air cleaner does not function.
Type set improper
AJ
Capacity data is wrongly proset. Or there is nothing programmed in the data hold IC.
C4
Sensor (R2T) for heat exchanger temperature is fault
C5
Sensor (R3T) for heat exchanger temperature is fault
C9
Sensor for suction air temperature is fault
Sensor for remote controller is fault
CJ
The remote controller thermistor does not function, but the system thermo run is possible.
E0
Action of safety device (outdoor unit)
E1
Outdoor unit's PC board faulty
E3
High pressure abnormal(outdoor unit)
E4
Low pressure abnormal (outdoor unit)
E5
Compressor motor lock malfunction
E6
Compressor motor lock by over current (outdoor)
Outdoor fan motor lock malfunction
E7
Outdoor fan instantneous overcurrent malfunction
E8
Input overcurrent (outdoor unit)
E9
Electronic expansion valve faulty (outdoor unit)
EA
Cooling/heating switch malfunction (outdoor)
F3
Discharge pipe temperature abnormal (outdoor unit)
H3
High pressure switch faulty (outdoor unit)
H4
Low pressure switch faulty (outdoor unit)
H6
Faulty position detection sensor (outdoor unit)
H7
Outdoor motor position signal malfunction
H8
CT abnormality (outdoor unit)
H9
Outdoor air thermistor faulty (outdoor unit)
J3
Discharge pipe thermistor faulty (outdoor unit)
J5
Suction pipe thermistor faulty (outdoor unit)
J6
Heat exchanger thermistor faulty (outdoor unit)
J8
Liquid piping thermistor malfunction (heating) (outdoor)
J9
Gas piping thermistor malfunction (cooling) (outdoor)
Overheated heat-radiating fin (outdoor)
L4
Inverter cooling defect.
Instantaneous overcurrent (outdoor)
L5
Possible earth fault or short circuit in the compressor motor.
Electric thermal (outdoor)
L8
Possible electrical overload in the compressor or cut line in the compressor motor.
Stall prevention (outdoor)
L9
Compressor possibly locked.