Commercial Fire Installation Guidelines

Dress field wiring away from the microprocessor (center) section of the PC board. Dress wiring to the left and right
sides of the cabinet and secure using tie wraps.
Separate all power-limited wiring from other wiring by at least ¼-inch (6.4mm).
Non-power-limited wiring that exits the control panel (i.e., facility power) must be run in conduit.
All unused knockouts must be plugged.
All wiring that exits the control panel must be strain-relieved (e.g., tie-wrapped).
Standoff
Standoffs
(3)
Wired to
Transformer

Figure 2-3: Circuit Board Installation