Step 1

Locating the
Fireplace
Clearance Requirements
The top and back of the fireplace
are defined by standoffs.
The heat shield must be at-
tached as shown if combustible
materials are placed directly on
top standoffs (Figure 3).
The minimum clearance to a
perpendicular wall extending
past the face of the fireplace is
7.62 cm.
The back of the fireplaces may
be recessed into combustible
construction, as shown below.
MODEL: SL-350TRS-CE-D
Minimum Clearances from the Fireplace to Combustible Materials
Glass
Front
91.4 cm
The diagram below shows space and clearance require-
ments for locating a fireplace within a room.
* NOTE: Dimensions
are shown with the
sides, back and/or
corners of the unit
13 mm from the
wall.
A
B
86.4 cm
41.3 cm
Figure 2.
Fireplace Dimensions, Locations, and
Space Requirements
TOP STANDOFFS
Figure 3. Heat Shield
back of
Floor
Fireplace
0
1.3 cm
Heat & Glo • SL-350TRS-CE-D • 2033-900 Rev. V • 3/13
7.6 cm
B
A
E
C
1.3 cm
C
D
72.8 cm
100.1 cm 141.6 cm
HEAT SHIELD
INSTALLED
HEAT SHIELD
RECESSED DEPTH: 41.3 cm
sides of
Top of
Fireplace
Fireplace
1.3 cm
8.9 cm
3
Installing the
Fireplace
D
E
ceiling
79 cm
10