Flue Pipe Clearances To Combustibles; Wall Penetration Framing - Heat & Glo SL-350TRS-CE-D Installer's Manual

Hide thumbs Also See for SL-350TRS-CE-D:
Table of Contents

Advertisement

B. Flue Pipe Clearances to Combustibles
wARNING
Fire Risk.
Explosion Risk.
Maintain flue pipe clearance to combustibles
as specified.
• Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials
away from flue pipe may cause fire.
Note: Heat shields MUST overlap by a minimum of 4 cm.
• DVP heat shield - designed to be used on a wall 10.2 cm to 18.4 cm) thick.
• If wall thickness is less than 10 cm, the existing heat shields must be field trimmed.
If wall thickness is greater than 18.4 cm, a DVP-HSM-B will be required.
• SLP heat shield - designed to be used on a wall 11.1 cm to 19.4 cm thick).
• If wall thickness is less than 11.1 cm, the existing heat shields must be field
trimmed. If wall thickness is greater than 19.4 cm, a DVP-HSM-B will be required.
(DVP-SLP Flue Shown)
Heat
Shield
7.6 cm)
top clearance
2.5 cm)
clearance around
vertical sections
Heat
Shield
* When using SLP flue, minimum clearances from the flue to combustible materials at
inside wall firestops are:
Figure 28 Horizontal Venting Clearances To Combustible
Materials
23
7.6 cm)
top clearance *
Heat
Shield
2.5 cm)
clearance
Wall
bottom & sides
Shield
Firestop
WALL
7.6 cm
top clearance *
Heat
Shield
2.5 cm
Wall
clearance
Shield
bottom & sides
Firestop
WALL
Top: 6.4 cm)
Bottom: 2.5 cm
Sides: 2.5 cm
Heat & Glo • SL-350TRS-CE-D • 2033-900 Rev. V • 3/13
C. wall Penetration Framing
2.54 cm
2.54 cm
A*
B*
A*
B*
105.4 cm 56.9 cm 102.9 cm 54.3 cm
* Shows center of flue pipe framing hole for top or rear venting. The
center of the hole is 2.54 cm above the center of the horizontal
flue pipe.
Figure 29 Exterior Wall Hole
Combustible wall Penetration
Frame a hole in a combustible wall for interior and exterior
wall shield firestops, (Figure 29) whenever a wall is pen-
etrated. Use same size framing materials as those used
in the wall construction. The wall shield firestops maintain
minimum clearances and prevent cold air infiltration.
Note: When penetrating a combustible wall, both interior and
exterior wall shield firestops are required.
Non-Combustible wall Penetration
If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter 2.5
cm greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield firestop is only required on one side and no heat
shield is necessary.
If your local inspector requires the wall shield firestop on
both sides, then both wall shield firestops must have a heat
shield attached to them.
C
D
C
D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents