Top Vent - Horizontal Termination
Venting with 1 elbow
Note: Use DVP Series
components only.
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance.
• This appliance requires a minimum of 24 inches of vertical
venting before attaching any elbow to the appliance.
Figure 4.5
Heatilator • CRAVE4836, CRAVE4836ST, CRAVE6048, CRAVE6048ST Installation Manual • 2301-970 Rev. E • 8/14
18
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe could cause fi re.
V
Minimum
1
2 ft.
610 mm
3 ft.
914 mm
4 ft.
1219 mm
5 ft.
1524 mm
6 ft.
1829 mm
7 ft.
2134 mm
8 ft.
2438 mm
V
+ H
= 63 ft. (19.2 m) Maximum
1
1
H
= 40 ft. (12.2 m) Maximum
1
WARNING
CRAVE4836
CRAVE6048
H
Maximum
1
1.5 ft.
457 mm
6 ft.
1.8 m
9 ft.
2.7 m
12 ft.
3.7 m
15 ft.
4.6 m
18 ft.
5.5 m
21 ft.
6.4 m
H
1
CRAVE4836ST
CRAVE6048ST
V
Minimum
H
1
1
2 ft.
610 mm
3 ft.
3 ft.
914 mm
6 ft.
4 ft.
1219 mm
9 ft.
5 ft.
1524 mm
12 ft.
6 ft.
1829 mm
15 ft.
7 ft.
2134 mm
18 ft.
8 ft.
2438 mm
21 ft.
V
+ H
= 63 ft. (19.2 m) Maximum
1
1
H
= 40 ft. (12.2 m) Maximum
1
V
1
Maximum
914 mm
1.8 m
2.7 m
3.7 m
4.6 m
5.5 m
6.4 m