10-1-4. Monitor Function of Remote Controller Switch
n Call of sensor temperature display
<Contents>
Each sensor temperature of the remote controller, indoor
unit, and outdoor unit can become known by calling the
service monitor mode from the remote controller.
<Procedure>
1
Push
+
buttons simultaneously for 4
seconds or more to call the service monitor
mode.
The service monitor goes on, the master indoor unit
No. is displayed, and then temperature of the item

code
is displayed.
2
Push the temperature setup
to select the sensor No. (Item code) of the sensor
to be monitored.
The sensor numbers are described below:
Item code
00
01
Indoor
02
unit data
03
04
*1 Only master unit in group control
3
The temperature of indoor units and outdoor unit in a group control can be monitored by pushing
button to select the indoor unit to be monitored.
4
Pushing
button returns the display to usual display.
/
buttons
Data name
Room temp (under control) *1
Room temp (remote controller)
Indoor suction temp
Indoor coil temp (TCJ)
Indoor coil temp (TC)
4
<Operation procedure>
1
Item code
60
61
Outdoor
62
unit data
63
64
65
– 64 –
SET DATA
UNIT No.
R.C.
No.
UNIT
SET
CL
1
3
2
3
4
Returned to usual display
Data name
Heat exchanger temp TE
Outside temp TO
Discharge temp TD
Suction temp TS
Heat sink temp THS