No.
Item
5
Air speed
selection
(Continued)
Value in the parentheses indicates one when thermostat of
the remote controller works.
Value without parentheses indicates one when thermostat
of the body works.
• If the air speed has been changed once, it is not
• When heating operation has started, the air speed
• If the temperature is just on the difference boundary, the
• Mode in the parentheses indicates one in automatic
• In Tc ≥ 60°C, the air speed increases by 1 step.
3) In heating operation, the mode changes to [UL] if
4) If Ta ≥ 25°C when heating operation has started and
5) In automatic cooling/heating operation, the revolution
Outline of specifications
<HEAT>
Ta (˚C)
L(L)
(-0.5)
–1.0
L(H)
(0)
Tsh
H(H)
(+0.5)
+1.0
H
(HH)
(+1.0)
+2.0
HH
(+1.5)
+3.0
(HH)
(+2.0)
+4.0
changed for 1 minute. However when the air speed is
exchanged, the air speed changes.
selects a upward slope, that is, the high position.
air speed does not change.
heating operation.
<Operation of duct only>
Air volume setup
Tap
COOL, DRY, FAN
F4
F5
F6
H
F7
M+
F8
F9
M
FA
FB
L+
FC
L
FD
thermostat is turned off.
when defrost operation has been cleared, it operates
with HIGH (H) mode or (HH) for 1 minute from when Tc
has entered in E zone of cool air discharge preventive
control (Item 6).
frequency of [HH] is set larger than that in the standard
cooling/heating operation. However the revolution
frequency is restricted in the automatic heating opera-
tion as shown in the following figure.
E
D
C
B
A
SM1100 SM1400
Revolutions per
HEAT
minute (rpm)
UH
530
660
H
510
660
500
620
M+
470
570
M
450
520
440
510
L+
410
470
L
390
430
380
420
UL
320
370
– 17 –
Remarks
Tc: Indoor heat exchanger
sensor temperature
[PRE-HEAT] display
F5
F4
Tc
(˚C)
47
42
F5