Diagnostic Codes - Lennox G43UF SERIES Unit Information

Hide thumbs Also See for G43UF SERIES:
Table of Contents

Advertisement

The integrated ignition control board is equipped with two LED lights for troubleshooting. The diagnostic codes are listed
below in table 4.
LED#1
32M88 − DS1 Green
78M47 − DS1 Red
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH
OFF
ALTERNATING
SLOW FLASH
SLOW FLASH
ON
ON
ON
OFF
FAST FLASH
SLOW FLASH
ALTERNATING
FAST FLASH
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
Low flame sense current = SureLight Control Board 32M88 0.16 − 0.17 microamps Ignition Control Board 78M47 & 100973−01 0.5 − 1.4 microamps
É É
Pre −Purge
ON
É É
É É
OFF
É É
É É É É É É É É É É É É É É É É É É É É É É É É
DEMAND
CAI
É É É É É É É É É É É É É É É É É É É É É É É É É É
É É É É É É É É É É É É É É É É É É É É É É É É
IGNITOR**
GAS VALVE
INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
** Ignitor on ignition control board 78M47 & 100973−01 equipped units will energize for the first 3 seconds of the 4
second trial, following the ignitor 20 second warm up .
TABLE 4

DIAGNOSTIC CODES

Make sure to Identify LED'S Correctly..
LED #2
32M88 − DS2 Green
78M47 − DS2 Green
Power on − Normal operation.
SIMULTANEOUS
Also signaled during cooling and continuous fan.
SLOW FLASH
SIMULTANEOUS
Normal operation − signaled when heating demand initiated at thermostat.
FAST FLASH
Primary or secondary limit switch open. Limit must close within 3 minutes or
ON
unit goes into 1 hour Watchguard.
Prove switch open.
SLOW FLASH
OR:Blocked inlet/exhaust vent;
OR: Prove switch closed prior to activation of combustion air inducer.
Watchguard −− burners failed to ignite
OR: limit open more than 3 minutes (control board 32M88 Only)
ALTERNATING
OR: lost flame sense 5 times in one heating cycle
SLOW FLASH
OR: prove switch opened 5 times in one heating cycle
OFF
Flame sensed without gas valve energized.
SLOW FLASH
Rollout switch open. OR: 12-pin connector improperly attached.
ON
OFF
Circuit board failure or control wired incorrectly.
ON
SLOW FLASH
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below
Control board 32M88 − 0.18 microamps
FAST FLASH
Control board 78M47 & 100973−01 − 1.5 microamps
Replace flame sense rod.
The following conditions are sensed
Improper main ground (control board 32M88) during the ignitor warm−up period
ONLY Improper main ground (control board 78M47 & 100973−01) continuously
OR: Broken ignitor (control board 32M88)
ALTERNATING
OR: Open ignitor circuit (control board 32M88)
FAST FLASH
OR: Line voltage to control below
Control board 32M88 75V
Control board 78M47 & 100973−01 90V
15 Sec.
20 sec.
Ignitor Warmup
É É É É É É É É É É
É É É É É É É É É É
DESCRIPTION
4 Sec.Trial
Blower On"
for Ignition
Delay
É É É É É É É É É É É É É
É É É É É É É É É É É É É
FIGURE 5
Page 11