Vitodens 200-W B2HA 19, 28, 35 Service
Check CO
Setting
2
The Vitodens 200-W, B2HA boiler is equipped with the
Combustion Management System developed by
Viessmann which ensures optimal combustion quality
independent of gas quality and type. (For a description of
the Combustion Management System, see page 30 in this
manual.) During initial start-up and maintenance you will
only need to check the CO
vent pipe adaptor.
Note: The Vitodens 200-W, B2HA boiler comes factory set
to operation with natural gas. (For instructions on how
to convert to operation with liquid propane gas, see
page 15). For high-altitude operation above 5,000 ft.
(1,500 m), see page 16. The MatriX cylinder burner
of this boiler is preset for the entire gas group. No
adjustment or readjustment of the burner is required.
and O
content at the boiler
2
2
1. Connect a flue gas analyzer to test port A at boiler
vent pipe adaptor.
2. Open gas shut-off valve, start up boiler and create
heat demand.
3. Selecting low/high fire:
Service menu
- Press OK and
simultaneously for approximately
4 seconds.
- "Actuator test"
- Selecting low fire: select "Base load OFF".
Then "Base load ON" appears and the burner
operates in low fire.
4. Measure CO
and O
2
2
adaptor. If the measured values deviated by more
than 1% from the ranges for the respective fuel
type listed in the right column or in the table on
page 30.
- check the venting system for leaks
(see subsection on page 20).
- check that the boiler is set for the gas type used
(see subsection on page 15).
CO
content range:
2
- 7.5 to 10.5% for natural gas
- 9.0 to 11.3% for LPG
O
content range:
2
- 3.8 to 7.3% for all gas types
5. Enter measured values into the Maintenance Record
on page 96. Terminate by selecting 'all actuators off'.
6. Selecting high fire: select "Full load OFF". Then
"Full load ON" appears and the burner operates in
high fire.
7. Measure CO
and O
2
2
adaptor. If the measured values deviated by more
than 1% from the ranges listed in the right column
or in the table on page 30.
- check the venting system for leaks
(see subsection on page 20).
- check that the boiler is set for the gas type used
(see subsection on page 15).
CO
content range:
2
- 7.5 to 10.5% for natural gas
- 9.0 to 11.3% for LPG
O
content range:
2
- 3.8 to 7.3% for all gas types
8. Press
to exit actuator test after testing and enter
measured values into the Maintenance Record on
page 97.
Start-up and Service
content at boiler vent pipe
content at boiler vent pipe